Companies & Downloads


Product Name
POP-6802
Products Description
Application:
The meter is used for precise dosing system which need to adjust the PH/ORP value accurately, the application fields including: Industry process, waste water treatment, Water Reuse Systems, Circuit Board waste water , electroplating waste water treatment, medical industry and etc. It can meet the requirements of backlash and dead area control in chemical, medicine reaction and neutralization process. And it is also meet the requirements of intelligent configuration transmitting control systems in PID close loop adjustment, difference value control, switch control, pulse frequency / duty cycle control, current transmitting, dosing tank level management.
 
Features:
Electronic chemical inline measurement +sensor + PLC+Professional software=system integration
Multi channels ( pH or ORP , pH+ORP,TEMP) sensors for inline measurement.
Dynamic PID adjustment, PWM pulse, controlling metering pump for accurate adjustment.
Professional solutions for electroplating process waste water treatment. Double channels ORP different value dynamic control
Driving solutions for various dosing pumps, Static switch, and PWM pulse selection.
Dosing tank low level alarm avoids dosing error
Multi-function sampling flow device needs only a little sample.

Flow chart of system control

Technical Data
 
Model: POP-6802
Case material: ABS
Installation: wall mounted or bottom installation
Protection level: IP65 (water proof nut wire in≥5mm)
pH measurement:    pH measurement:pH sensor
    pH range :2.0 ~ 12.0
    Resolution:pH: 0.02
    Accuracy:pH:±0.2
    temperature:0 ~ 40
 
ORP measurement:    ORP measurement:ORP sensor
ORP range:-1999mV ~ +1999mV
Accuracy:±5mV        
Resolution:1mV                 
Stability:±5mV/24h 
Temperature:0 ~ 40
 
Water temperature measurement:  Component:Pt1000
Accuracy:±0.5℃
Range:0~99.9℃
Resolution:0.1
Stablility: ±5℃/24h
Switch signal input:
Pull-up Voltage12VDC, photoelectricity seclu-sion
Dosing tank low level switch:3 channels (installed at bottom to monitor the level)
Level switch (normal open):double channels (monitoring level)

Switch signal output:
Relay output:3 channels
Dry Contact output,Load capability:3A/AC 240V(max)
3A/DC 30V(max)
OC output:2 channels
External power supply,load current 25mA( at DC 5V)load voltage DC24V(Max)
 
Analog Communication:
4-20mA output
Double channels, isolated, configuration, transferable,
reversible, inside/outside power supply selectable .max.
loop impedance 300oHm, accuracy< ±1%
 
Communication port: RS-485 serial interface ,one channel
 
Interface:
240x160 LCD display,backlight white/green can be set,
six digits graphics button.
 
Working environment: temperature:0~60℃   humidity ≤90%RH
Power supply: AC/DC 18V~36V;Power consumption:≤5W
Dimension: 235mm×185mm×119mm (H×W×D)
Weight: 5kg
 
 
 
 
??????? ???????? ?????? ?????
????? ??????
 03-6764586
?? ????
 03-6771280
 







Pumps

Flow and Level

Valves & Fittings

Air and Gas Handling & Managment

Water Treatment & Filtration

- Siemens

- ATG UV Technology

- CLEAR LAKE Filtration

- Createc

- Pentair

- GE

- EUROTROL

Orbital Welding

Stock Products For sale

 

 

 

 

 

© כל הזכויות שמורות לחברת סמל בע"מ

 

Home   |    Products   |    About us   |    News   |    Companies & Downloads   |    Sitemap   |    Terms & Conditions   |    Contact Us   |    Privacy Policy